Title of article :
Thermodynamic design data and performance evaluation of the water + lithium bromide + lithium iodide + lithium nitrate + lithium chloride system for absorption chiller
Author/Authors :
H.-R. Lee، نويسنده , , K.-K. Koo، نويسنده , , S. Jeong، نويسنده , , J.-S. Kim، نويسنده , , H. Lee، نويسنده , , Y.-S. Oh، نويسنده , , D.-R. Park، نويسنده , , Y.-S. Baek، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
Dühring (P–T–X) and enthalpy-concentration (H–X–T) diagrams of the H2O + LiBr + LiNO3 + LiI + LiCl (mole ratio of LiBr : LiNO3 : LiI : LiCl = 5 : 1 : 1 : 2) system were constructed by using the experimental data sets. Thermodynamic design data for a double-effect series-flow absorption chiller were calculated at various operating conditions [ 2≤Te≤14°C, 30≤Ta≤50°C, 30≤Tc≤50°C, TghCOP=0≤Tgh≤Tgh (crystallization limit)] by a computer simulation. The proposed working fluid was found to be applicable to cycle operation of air-cooled absorption chiller with no crystallization problem at higher absorber temperature.
Keywords :
Air-cooled absorption chiller , Crystallization , Thermodynamic design data , Working fluid
Journal title :