• Title of article

    Experimental investigation of two phase flow condensation of alternatives to HCFC-22 inside enhanced surface tubing

  • Author/Authors

    Samuel M. Sami، نويسنده , , Hector Maltais، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2000
  • Pages
    14
  • From page
    1113
  • To page
    1126
  • Abstract
    This paper presents an experimental study of two phase flow condensation of some alternative zeotropic refrigerant mixtures to R-22, inside air/refrigerant horizontal enhanced surface tubing. The alternatives considered in this study are; R-507, R-404A, R-407C, and R-408A as well as R-410A. It was evident from the condensation experimental data that R-408A has the highest heat transfer rate compared to the other blends under the investigated range of refrigerant mass flow rates and heat flux. However, when the thermophysical properties are factored in, the condensation data showed that R-410A has the highest heat transfer rate at Reynolds number higher than 2.35E+7 Furthermore, experimental data of two phase condensation pressure gradient data across the test section at different Reynolds numbers showed that R-410A has the highest convective pressure drop among the blends under investigation.
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2000
  • Journal title
    Applied Thermal Engineering
  • Record number

    1023248