Title of article :
How varying condenser coolant flow rate affects chiller performance: thermodynamic modeling and experimental confirmation
Author/Authors :
J.M Gordon، نويسنده , , K.C Ng، نويسنده , , H.T Chua، نويسنده , , CK Lim، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
11
From page :
1149
To page :
1159
Abstract :
Although most commercial chillers are designed and installed to operate at constant coolant flow rates, one can alter the power consumption of their compressors by modifying the design to incorporate variable coolant flow rates. The issue addressed here is how to model that explicit flow-rate dependence within an analytic chiller model. We expand our earlier thermodynamic model to explicitly account for the influence of condenser coolant flow rate, and validate model predictions against an extensive set of experimental measurements from a large commercial centrifugal chiller.
Keywords :
Flow rate , Chiller , condenser , Centrifugal , Thermodynamic modeling , Heat exchanger , Coolant
Journal title :
Applied Thermal Engineering
Serial Year :
2000
Journal title :
Applied Thermal Engineering
Record number :
1023250
Link To Document :
بازگشت