Title of article :
Experimental analysis of a bubble pump operated H2O–LiBr vapour absorption cooler
Author/Authors :
R. Saravanan، نويسنده , , M.P. Maiya، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Pages :
15
From page :
2383
To page :
2397
Abstract :
Experimental analysis of a H2O–LiBr vapour absorption cooler based on bubble pump technique and hydrostatic principle are presented. Heat input to the bubble pump and boiler, pump lift/driving head and weak solution concentration are varied to analyze the system performance. The cooler is tested at different load conditions, i.e., at no load, pull down load and steady load conditions. Results indicate that coefficient of performance of about 0.50 could be attained for the boiler temperature of 85 °C and condenser and absorber temperatures in excess of 40 °C.
Keywords :
Absorption cooler , Pumpless refrigerator , Water–lithium bromide , Driving head , Bubble pump , COP , Pump lift
Journal title :
Applied Thermal Engineering
Serial Year :
2003
Journal title :
Applied Thermal Engineering
Record number :
1025783
Link To Document :
بازگشت