Title of article :
Experimental analysis of a bubble pump operated H2O–LiBr vapour absorption cooler
Author/Authors :
R. Saravanan، نويسنده , , M.P. Maiya، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Abstract :
Experimental analysis of a H2O–LiBr vapour absorption cooler based on bubble pump technique and hydrostatic principle are presented. Heat input to the bubble pump and boiler, pump lift/driving head and weak solution concentration are varied to analyze the system performance. The cooler is tested at different load conditions, i.e., at no load, pull down load and steady load conditions. Results indicate that coefficient of performance of about 0.50 could be attained for the boiler temperature of 85 °C and condenser and absorber temperatures in excess of 40 °C.
Keywords :
Absorption cooler , Pumpless refrigerator , Water–lithium bromide , Driving head , Bubble pump , COP , Pump lift
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering