Title of article
Influence of the cooling circulation water on the efficiency of a thermonuclear plant
Author/Authors
J. Ganan، نويسنده , , A. Rahman Al-Kassir، نويسنده , , J.F. Gonzalez، نويسنده , , A. Mac??as، نويسنده , , M.A. Diaz، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
10
From page
485
To page
494
Abstract
In the present study, the feasibility of intercalating two cooling towers in the present circulation water system used at Almaraz Nuclear Power Plant, located at Campo Arañuelo district (SW Spain), has been technically evaluated in order to increase the efficiency of the thermodynamic cycle used at present. Thus, the working cycle has been analyzed, the power produced by the turbines being calculated as a function of the cooling circulation water temperature. Next, two natural convection counterflow cooling towers have been calculated in order to be installed in parallel with the present cooling system (Lake Arrocampo). The power obtained in the turbines provided with the new system has been estimated. Finally, a system combining both the cooling towers and the Lake Arrocampo has been proposed, the increment in power using one system or the other according to the weather conditions being calculated.
Keywords
Power , Condenser vacuum , Cooling system , Efficiency
Journal title
Applied Thermal Engineering
Serial Year
2005
Journal title
Applied Thermal Engineering
Record number
1026034
Link To Document