Title of article :
On-line detection of fouling in a water circulating temperature controller (WCTC) used in injection moulding: Part 2: Application
Author/Authors :
Sylvain Lalot b، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2006
Pages :
11
From page :
1095
To page :
1105
Abstract :
The technique presented in this paper aims at alerting the user that fouling has modified the capabilities of a WCTC, pointing out the affected component so that predictive maintenance can be carried out, reducing the exploitation costs of the WCTC. The technique presented in the first part (principles) is applied. In a first step, the characteristic vector of the WCTC is determined. In a second step, experimental results that validate the technique are presented.
Keywords :
On-line , Fouling , Neural network , Detection , Heat exchanger
Journal title :
Applied Thermal Engineering
Serial Year :
2006
Journal title :
Applied Thermal Engineering
Record number :
1040608
Link To Document :
بازگشت