Title of article :
Constraints of using thermostatic expansion valves to operate air-cooled chillers at lower condensing temperatures
Author/Authors :
F.W. YuCorresponding author contact information، نويسنده , , E-mail the corresponding author، نويسنده , , K.T. Chan، نويسنده , , H.Y. Chu، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2006
Pages :
9
From page :
2470
To page :
2478
Abstract :
Thermostatic expansion valves (TXVs) have long been used in air-cooled chillers to implement head pressure control under which the condensing temperature is kept high at around 50 °C by staging condenser fans as few as possible. This paper considers how TXVs prevent the chillers from operating with an increased COP at lower condensing temperatures when the chiller load or outdoor temperature drops. An analysis on an existing air-cooled reciprocating chiller showed that the range of differential pressures across TXVs restricts the maximum heat rejection airflow required to increase the chiller COP, though the set point of condensing temperature is reduced to 22 °C from a high level of 45 °C. It is possible to use electronic expansion valves to meet the differential pressure requirements for maximum chiller COP. There is a maximum of 28.7% increase in the chiller COP when the heat rejection airflow is able to be maximized in various operating conditions. The results of this paper emphasize criteria for lowering the condensing temperature to enhance the performance of air-cooled chillers.
Keywords :
Differential pressure , Thermostatic expansion valve , Condensing temperature , Air-cooled chiller
Journal title :
Applied Thermal Engineering
Serial Year :
2006
Journal title :
Applied Thermal Engineering
Record number :
1040949
Link To Document :
بازگشت