• Title of article

    The thermal effects of some control logics used in GDHS

  • Author/Authors

    Serhan Küçüka، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2007
  • Pages
    6
  • From page
    1495
  • To page
    1500
  • Abstract
    The temperature of the water returning from the network affects greatly the efficiency of a geothermal district-heating system (GDHS). The temperature of the returning water depends on whether there is a heat exchanger between network flow and indoor circulation. The return temperature also depends on outdoor temperature and logic of the indoor temperature control system. In this paper, four control logics are defined depending on whether indoor circulation is separated from network circulation or not. Return temperature and circulation rate of network flow are calculated for these control logics. The results show that the flow rate of the network flow and annual consumption of the geothermal fluid could be decreased about 10% or over by using optimum control logic in district heating systems.
  • Keywords
    District heating , Geothermal heating , Balçova GDHS
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2007
  • Journal title
    Applied Thermal Engineering
  • Record number