Title of article
Air heat exchangers with long heat pipes: Experiments and predictions
Author/Authors
H. Hagens، نويسنده , , F.L.A. Ganzevles، نويسنده , , C.W.M. van der Geld، نويسنده , , M.H.M. Grooten، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2007
Pages
9
From page
2426
To page
2434
Abstract
This paper presents measurements and predictions of a heat pipe-equipped heat exchanger with two filling ratios of R134a, 19% and 59%. The length of the heat pipe, or rather thermosyphon, is long (1.5 m) as compared to its diameter (16 mm). The airflow rate varied from 0.4 to 2.0 kg/s. The temperatures at the evaporator side of the heat pipe varied from 40 to 70 °C and at the condenser part from 20 to 50 °C. The measured performance of the heat pipe has been compared with predictions of two pool boiling models and two filmwise condensation models. A good agreement is found. This study demonstrates that a heat pipe equipped heat exchanger is a good alternative for air–air exchangers in process conditions when air–water cooling is impossible, typically in warmer countries.
Keywords
Finned tube , Heat exchanger , R-134a , Thermosyphon , Heat pipe
Journal title
Applied Thermal Engineering
Serial Year
2007
Journal title
Applied Thermal Engineering
Record number
1041438
Link To Document