Title of article :
An empirical model for independent control of variable speed refrigeration system
Author/Authors :
Hua Li، نويسنده , , Seok Kwon Jeong، نويسنده , , Jung-In Yoon، نويسنده , , Sam-Sang You، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Pages :
7
From page :
1918
To page :
1924
Abstract :
This paper deals with an empirical dynamic model for decoupling control of the variable speed refrigeration system (VSRS). To cope with inherent complexity and nonlinearity in system dynamics, the model parameters are first obtained based on experimental data. In the study, the dynamic characteristics of indoor temperature and superheat are assumed to be first-order model with time delay. While the compressor frequency and opening angle of electronic expansion valve are varying, the indoor temperature and the superheat exhibit interfering characteristics each other in the VSRS. Thus, each decoupling model has been proposed to eliminate such interference. Finally, the experiment and simulation results indicate that the proposed model offers more tractable means for describing the actual VSRS comparing to other models currently available.
Keywords :
Coefficient of performance (COP) , Decoupling model , Superheat control , Capacity control , Variable speed refrigeration system (VSRS)
Journal title :
Applied Thermal Engineering
Serial Year :
2008
Journal title :
Applied Thermal Engineering
Record number :
1041711
Link To Document :
بازگشت