Title of article
Performance of a residential heat pump operating in the cooling mode with single faults imposed
Author/Authors
Minsung Kim، نويسنده , , W. Vance Payne، نويسنده , , Piotr A. Domanski، نويسنده , , Seok Ho Yoon، نويسنده , , Christian J.L. Hermes، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2009
Pages
9
From page
770
To page
778
Abstract
The system behavior of a R410A residential unitary split heat pump operating in the cooling mode was investigated. Seven artificial faults were implemented: compressor/reversing valve leakage, improper outdoor air flow, improper indoor air flow, liquid line restriction, refrigerant undercharge, refrigerant overcharge, and presence of non-condensable gas in the refrigerant. This study monitored eight fault detection features and identified the most sensitive features for each fault. The effect of the various fault levels on energy efficiency ratio (EER) was also estimated. Since the studied system employed a thermostatic expansion valve (TXV) as an expansion device, it could adapt to some faults making the fault less detectable. The distinctiveness of the fault depended on the TXV status (fully open or not).
Keywords
Heat pump , Rule-based decision chart , Thermostatic expansion valve , Fault detection and diagnosis
Journal title
Applied Thermal Engineering
Serial Year
2009
Journal title
Applied Thermal Engineering
Record number
1041859
Link To Document