• Title of article

    Performance of a residential heat pump operating in the cooling mode with single faults imposed

  • Author/Authors

    Minsung Kim، نويسنده , , W. Vance Payne، نويسنده , , Piotr A. Domanski، نويسنده , , Seok Ho Yoon، نويسنده , , Christian J.L. Hermes، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    9
  • From page
    770
  • To page
    778
  • Abstract
    The system behavior of a R410A residential unitary split heat pump operating in the cooling mode was investigated. Seven artificial faults were implemented: compressor/reversing valve leakage, improper outdoor air flow, improper indoor air flow, liquid line restriction, refrigerant undercharge, refrigerant overcharge, and presence of non-condensable gas in the refrigerant. This study monitored eight fault detection features and identified the most sensitive features for each fault. The effect of the various fault levels on energy efficiency ratio (EER) was also estimated. Since the studied system employed a thermostatic expansion valve (TXV) as an expansion device, it could adapt to some faults making the fault less detectable. The distinctiveness of the fault depended on the TXV status (fully open or not).
  • Keywords
    Heat pump , Rule-based decision chart , Thermostatic expansion valve , Fault detection and diagnosis
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2009
  • Journal title
    Applied Thermal Engineering
  • Record number