Title of article :
A study on the performance enhancement of heat pump using electric heater under the frosting condition: Heat pump under frosting condition
Author/Authors :
Kyungmin Kwak، نويسنده , , Cheolho Bai، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Abstract :
The purpose of the present study is to enhance the heating capacity and increase COP under the frosting condition during heating operation of small capacity air-to-air heat pump. We applied an electric heater in front of outdoor unit of heat pump instead of indoor unit as usual. When the outdoor temperature is 2 °C/1 °C (DB/WB), the present heat pump turns on the electric heater in outdoor unit. The heating capacity increases 38.0% and COP increases 57.0% in comparison with those of conventional heat pump. When the outdoor temperature is 4 °C/2 °C (DB/WB), the electric heater is in ON/OFF mode according to the temperature of the evaporator. The heating capacity increases 9.1% and COP increases 71.1% in comparison with those of conventional heat pump.
Keywords :
Heat capacity , COP , Heat pump , Defrosting , Electric heater
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering