Title of article :
Experimental investigation of single phase convective heat transfer coefficient in a corrugated plate heat exchanger for multiple plate configurations
Author/Authors :
T.S. Khan، نويسنده , , M.S. Khan، نويسنده , , Ming-C. Chyu، نويسنده , , Z.H. Ayub، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Abstract :
Corrugated plate heat exchangers have larger heat transfer surface area and increased turbulence level due to the corrugations. In this study, experimental heat transfer data are obtained for single phase flow (water-to-water) configurations in a commercial plate heat exchanger for symmetric 30°/30°, 60°/60°, and mixed 30°/60° chevron angle plates. Experiments were carried out for Reynolds number ranging from 500 to 2500 and Prandtl number from 3.5 to 6.5. Experimental results show significant effect of chevron angle and Reynolds number on the heat transfer coefficient. Based on the experimental data, a correlation to estimate Nusselt number as a function of Reynolds number, Prandtl number and chevron angle has been proposed.
Keywords :
Plate heat exchanger , Single phase , Heat transfer , Nusselt number , Chevron angle
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering