Title of article :
Thermal and economic evaluation of heat recovery measures for indoor ice rinks
Author/Authors :
Olivier Piché، نويسنده , , Nicolas Galanis، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Pages :
6
From page :
2103
To page :
2108
Abstract :
A comparative study of three ventilation systems supplying air to a typical Canadian indoor ice rink illustrates the power, energy and operating cost savings which can be achieved by using the relatively warm air from the air cooled condensers of the refrigeration system. The direct use of this warm air for ventilation results in a reduction of energy consumption during the winter amounting to 24.2% of the yearly consumption of the heating system. On the other hand, the use of a heat exchanger to heat the ventilation air results in energy consumption reductions throughout the year. Depending on the size of the heat exchanger these gains can be as high as 60.8% of the heating energy consumption by the existing system. Based on actual prices of electricity and the heat exchanger it is established that the cost savings over the life of the equipment are at least three times higher than the cost of the heat exchanger.
Keywords :
Ventilation , Heat recovery , Energy efficiency , Building , simulation
Journal title :
Applied Thermal Engineering
Serial Year :
2010
Journal title :
Applied Thermal Engineering
Record number :
1045269
Link To Document :
بازگشت