Title of article :
Experimental results of an activated carbon–HFC 134a adsorption cooling system for thermal management of electronics
Author/Authors :
N.D. Banker، نويسنده , , M. Prasad، نويسنده , , P. Dutta، نويسنده , , K. Srinivasan، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
6
From page :
1607
To page :
1612
Abstract :
Results of performance measurement of a small cooling capacity laboratory model of an adsorption refrigeration system for thermal management of electronics are compiled. This adsorption cooler was built with activated carbon as the adsorbent and HFC 134a as the refrigerant to produce a cooling capacity under 5 W using waste heat up to 90 °C. The thermal compression process is obtained from an ensemble of four solid sorption compressors. Parametric study was conducted with cycle times of 16 and 20 min, heat source temperatures from 73 to 87 °C and cooling loads from 3 to 4.9 W. Overall system performance is analyzed using two indicators, namely, cooling effectiveness and normalized exergetic efficiency.
Keywords :
Adsorption , Refrigeration , HFC 134a , Activated carbon , Thermal management