Title of article :
Hyperbolic boiler tube leak location based on quaternary acoustic array
Author/Authors :
Liansuo An، نويسنده , , Peng Wang، نويسنده , , Augusto Sarti، نويسنده , , Fabio Antonacci، نويسنده , , Jie Shi، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
9
From page :
3428
To page :
3436
Abstract :
Early detection and location of a boiler leak help reduce possible equipment damage and productivity loss. In the present study, a four-element acoustic array and a set of hyperbolic equations were used to locate a power plant boiler leak. Maximum likelihood (ML) and phase transformation (PHAT) estimators were used to localize the leak source. Error rate and root mean square error (RMSE) evaluation revealed the superiority of ML over PHAT in the noisy and lowly reverberant boiler environment. To avoid distant source assumption, a genetic algorithm (GA) modified by an adaptive Gaussian mutation operator was used to search for the global hyperbolic optimum by probability calculations. The GA slightly outperformed the quasi-Newton method and required more time to converge. However, selecting a starting point near the true position is not simple in practice, and iterative process convergence is not assured in the quasi-Newton method. Time delay estimator errors greatly influence localization accuracy. The quaternary plane array localization error was within the permitted range of 0.01 ms, whereas that of the stereo array was 0.1 ms. Compared with the quaternary plane, the stereo array was more robust and accurate, but required more time to converge.
Keywords :
Hyperbolic location , Boiler leakage , Quaternary acoustic array , Genetic algorithm (GA) , Maximum likelihood (ML) estimator , Time differences of arrival (TDOA)
Journal title :
Applied Thermal Engineering
Serial Year :
2011
Journal title :
Applied Thermal Engineering
Record number :
1045764
Link To Document :
بازگشت