Title of article :
Hybrid liquid desiccant air-conditioning system: Experiments and simulations
Author/Authors :
Seiichi Yamaguchi، نويسنده , , Jongsoo Jeong، نويسنده , , Kiyoshi Saito، نويسنده , , Hikoo Miyauchi، نويسنده , , Masatoshi Harada، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
7
From page :
3741
To page :
3747
Abstract :
This study focuses on a hybrid liquid desiccant air-conditioning system consisting of a conventional liquid desiccant system and a vapour compression heat pump. The hybrid liquid desiccant air-conditioning system is expected to enhance the system efficiency of a conventional liquid desiccant system. In this study, the liquid desiccant is aqueous solution of lithium chloride and the refrigerant of the vapour compression heat pump is R407C. The main feature of this system is that the absorber and regenerator are integrated with the evaporator and condenser respectively. The performance evaluation test is conducted to obtain the primary data. Additionally, the improvement method for the system efficiency is discussed by the mathematical calculations. As a result, the system can dehumidify 5.9 g/kg(DA) under the conditions of summer in Tokyo, Japan. Then, the calculation results show that COPs can become higher by improving the compressor isentropic efficiency and the temperature efficiency of solution heat exchanger.
Keywords :
Dehumidification , Liquid desiccant , Air-conditioning , Heat pump , simulation
Journal title :
Applied Thermal Engineering
Serial Year :
2011
Journal title :
Applied Thermal Engineering
Record number :
1045801
Link To Document :
بازگشت