• Title of article

    Experimental research of the cross walls effect on the thermal performance of wet cooling towers under crosswind conditions

  • Author/Authors

    Youliang Chen، نويسنده , , Fengzhong Sun، نويسنده , , Hongguo Wang، نويسنده , , Nasi Mu، نويسنده , , Ming Gao، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2011
  • Pages
    7
  • From page
    4007
  • To page
    4013
  • Abstract
    This paper describes a hot model test of natural draft wet cooling towers (NDWCTs) to investigate the effect of cross walls on the thermal performance of NDWCTs under crosswind conditions. The hot model test can simulate the actual operation of a prototype tower by operating a model tower at steady state conditions while varying the temperature and flow rate of the incoming hot water along with the crosswind velocity. Cross walls of two shapes at different setting angles were installed in the rain zone and tested under various operating conditions. The results show that crosswinds degrade the NDWCT performance below a critical crosswind velocity Vcr, but improve the performance above Vcr. Increasing water flow rate and inlet water temperature can raise Vcr. Installing cross walls can improve the NDWCT performance. At low crosswind velocities, the solid wall leads to better NDWCT performance than the porous wall. However, the opposite effect is obtained at high crosswind velocities. At all crosswind velocities, the cross wall at a setting angle of 0° results in higher performance than that at 45°, regardless of cross wall shapes. Moreover, the cross wall at 45° degrades the NDWCT performance under high crosswind conditions.
  • Keywords
    Cross wall , Natural draft , Wet , Thermal performance , Cooling tower , Crosswind velocity
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2011
  • Journal title
    Applied Thermal Engineering
  • Record number