Title of article
Two-phase supply of three-phase transformers. Part 2: Wound core type transformers
Author/Authors
P.، Raitsios, نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
6
From page
607
To page
612
Abstract
The three-phase supply of distribution transformers sometimes changes unexpectedly to two-phase supply, due to external reasons, e.g. a burned fuse or interruption of one of the phases. In this case secondary voltages result which are no longer equal to the nominal phase voltage in all phases, i.e. the one voltage is still equal to the nominal, while the two others are not, but their vector sum is equal to the nominal voltage, since it is obtained from the same primary polar voltage. This occurs for all connections except the star-star connection, for which none of the secondary voltages is equal to the nominal phase voltage. The magnitude of each voltage depends on the ampere-turns, the core dimensions and the magnetic permeability that appears in each core branch (limb). These voltages are calculated from the equivalent magnetic circuit and the magnetising curve of the core material.
Keywords
Hydrograph
Journal title
IEE Proceedings Electric Power Applications
Serial Year
2004
Journal title
IEE Proceedings Electric Power Applications
Record number
106471
Link To Document