Title of article
Velocity effect on electronic-antifouling technology to mitigate mineral fouling in enhanced-tube heat exchanger
Author/Authors
Sung H Lee، نويسنده , , Young I Cho، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2002
Pages
12
From page
4163
To page
4174
Abstract
The purpose of the present study was to investigate the effect of flow velocity on an electronic-antifouling (EAF) treatment, which was considered to mitigate mineral fouling in a heat exchanger with cooling-tower water. Nine different tests were conducted with no-blowdown: six runs with an in-line EAF treatment and three runs with the EAF treatment at a side-stream loop. The flow velocities tested were 0.6, 1.2, 1.5 and 2.0 m/s. As the flow velocity was increased, the benefit of the in-line EAF treatment decreased. At a flow velocity of 0.6 m/s, the fouling resistance decreased by 80% in the case with the EAF treatment compared with that in the no-treatment case for both in-line and side-stream EAF treatments.
Keywords
Enhanced tube , Electronic-antifouling , Heat exchanger , Fouling , Flow velocity
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year
2002
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number
1071182
Link To Document