Title of article :
Optimal spray characteristics in water spray cooling
Author/Authors :
Ruey-Hung Chen، نويسنده , , Louis C. Chow، نويسنده , , Jose E. Navedo، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
The dependence of the efficiency of liquid usage (η) at CHF on spray parameters was experimentally investigated for subcooled water spray cooling. A spray can be characterized by three independent parameters (droplet Sauter-mean diameter, d32, droplet velocity, V, and droplet flux, N). In this study, each of these parameters was varied with the other two kept constant by using a combination of spray nozzles, operating pressures, and distance between the nozzle exit and the heater surface. It was found that η varies with N−2/3, image and V1/4, respectively, when two of the three spray parameters are kept nearly constant. It was also found that CHF varies with N1/6 and V1/4 and is relatively independent of d32. It is concluded that to achieve the maximum possible CHF while using the minimum quantity of water, it is desirable to select nozzles that produce as small a droplet diameter with as high a velocity as possible.
Keywords :
Critical heat flux , Boiling , Droplet , Efficiency , Scaling , Spray
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER