Title of article
An experimental investigation on capillary pumped loop with the meshes wick
Author/Authors
Jianlin Yu، نويسنده , , Hua Chen، نويسنده , , Hua Zhao، نويسنده , , Yanzhong Li، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2007
Pages
5
From page
4503
To page
4507
Abstract
A copper-water capillary pumped loop (CPL) is developed for heat recovery applications in the field of the refrigeration and air conditioning. The multi-layer copper meshes are used as the capillary structure in the CPL. The startup characteristics and heat transfer performance of the CPL are investigated experimentally. The experimental results show that for a range of power applied to the evaporator, the system presented reliable startups and continuous operation. The heat transfer performance of the evaporator will be improved if the charging rate of the working fluid or the heat flux is increased properly. The optimal charging rate could be obtained in the range of 70–76% for the given experimental conditions. The study has demonstrated the proposed CPL configuration is able to perform the heat recovery applications.
Keywords
Heat transfer , Heat recovery , Capillary pumped loop
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year
2007
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number
1075087