Title of article :
Effect of a delta-winglet vortex pair on the performance of a tube–fin heat exchanger
Author/Authors :
C.B. Allison، نويسنده , , B.B. Dally، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2007
Pages :
8
From page :
5065
To page :
5072
Abstract :
The experimental analysis of the effects of delta-winglet vortex generators on the performance of a fin and tube radiator is presented. The winglets were arranged in flow-up configuration, and placed directly upstream of the tube. This is a hitherto untested configuration, but is thought to have certain advantages. In addition to vortex generation the flow is guided onto the tube surface increasing the localised velocity gradients and Nusselt numbers in this region. The study includes dye visualisation and full scale heat transfer performance measurements. The results are compared to a standard louvre fin surface. It was found that the winglet surface had 87% of the heat transfer capacity but only 53% of the pressure drop of the louvre fin surface.
Keywords :
Compact tube–fin heat exchanger , Delta-winglet vortex generator
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year :
2007
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number :
1075142
Link To Document :
بازگشت