Title of article :
Corrections to the simple effectiveness-NTU method for counterflow cooling towers and packed bed liquid desiccant–air contact systems
Author/Authors :
Cheng-Qin Ren، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Pages :
9
From page :
237
To page :
245
Abstract :
Analytical expressions for the corrections to the simple effectiveness-NTU method are developed using perturbation technique for cooling towers and liquid desiccant–air contact systems. The developed model takes into consideration the effect of nonlinearities of humidity ratio and enthalpy of air in equilibrium with water or desiccant solutions. The model also takes into consideration the effect of water loss by evaporation and the effect of variation of the specific heat capacity of water or solution. The comparison with numerical integration of the dimensional heat and mass transfer equations shows that the analytical results are generally satisfactory and the improvement over the simple ε-NTU method is significant.
Keywords :
Cooling towers and liquid desiccant–air contact systems , Heat and mass transfer , Effectiveness-NTU method , Corrections , Perturbation technique
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year :
2008
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number :
1075191
Link To Document :
بازگشت