Title of article
Development and validation of static simulation model for CO2 heat pump
Author/Authors
Seiichi Yamaguchi، نويسنده , , Daisuke Kato، نويسنده , , Kiyoshi Saito، نويسنده , , Sunao Kawai، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2011
Pages
11
From page
1896
To page
1906
Abstract
A simulation model for the CO2 heat pump water heater was developed and validated in this study. Component models of the gas cooler, evaporator, compressor, and expansion valve were constructed with careful consideration for the heat transfer performances. To validate the simulation model, experiments were carried out using an actual CO2 heat pump water heater (water heating capacity: 22.3 kW; hot-water temperature: 90 °C). In simulations and experiments, the effects of the inlet water temperature and outside air temperature on the system characteristics were discussed. As a result, the average difference in COP between the simulation results and experimental results is 1.5%.
Keywords
CO2 , Heat pump , Water heater , validation , simulation
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year
2011
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number
1077201