Title of article
Numerical simulation of a closed wet cooling tower with novel design
Author/Authors
Z.Z. Xia، نويسنده , , C.J. Chen، نويسنده , , R.Z. Wang، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2011
Pages
8
From page
2367
To page
2374
Abstract
A closed wet cooling tower with novel design was proposed and numerically investigated. The studied cooling tower consists of two main parts: one heat and mass transfer unit (HMTU) and one heat transfer unit (HTU). In the HMTU, copper tubes are arranged as heat transfer tubes while plastic tubes are collocated to enlarge the mass transfer area between the spray water and the airflow. In the HTU, only copper tubes are adopted as heat transfer tubes. Heat and mass transfer process takes place among the process water, airflow and spray water in the HMTU, while in the HTU only heat transfer between the process water and the spray water is observed. A transient one dimensional distributed-parameter model was adopted to evaluate the cooling tower performance under different operating conditions. Determination of heat and mass transfer coefficients, as well as the influence of Lewis number on the cooling tower performance, was presented.
Keywords
Cooling tower , Numerical , Heat and mass transfer , Transient , Lewis number
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year
2011
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number
1077255
Link To Document