Title of article :
Modeling of a flat plate membrane-distillation system for liquid desiccant regeneration in air-conditioning applications
Author/Authors :
Alexander S. Rattner، نويسنده , , Ananda Krishna Nagavarapu، نويسنده , , Srinivas Garimella، نويسنده , , Thomas F. Fuller، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
11
From page :
3650
To page :
3660
Abstract :
A thermally driven flat plate air gap membrane distillation liquid desiccant regenerator for lithium chloride in dehumidification applications is modeled. Operating conditions and device geometry are optimized, and it is found that membrane materials have little influence on regenerator performance. It is shown that radiation heat transfer across the air gap cannot be neglected. The regenerator removes 11.4 g min−1 cm−3 of moisture with a COP of 0.372 for an inlet solution concentration of 0.38, solution flow rate of 50 ml min−1, and heated solution temperature of 135 °C. This design has negligible desiccant carry-over losses and operates without a blower.
Keywords :
Waste heat recovery , Liquid desiccants , Desiccant air conditioning , Membrane distillation
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year :
2011
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number :
1077383
Link To Document :
بازگشت