Title of article :
Optimal thermal operation of liquid-cooled electronic chips
Author/Authors :
Chander Shekhar Sharma، نويسنده , , Severin Zimmermann، نويسنده , , Manish K. Tiwari، نويسنده , , Bruno Michel، نويسنده , , Dimos Poulikakos، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2012
Pages :
13
From page :
1957
To page :
1969
Abstract :
A novel framework is developed to determine the optimal operating conditions of water cooled microprocessor chips through a tradeoff between heat recovery from the coolant and the chip thermal reliability. For illustration, a manifold microchannel heat sink is evaluated experimentally and computationally. First, a single objective optimization is demonstrated by combining the heat recovery and chip reliability into a single parameter. Then, multi-objective optimizations are performed by using Pareto optimality and Multi-Criteria Design Analysis. Using conservative guidelines, these approaches suggest that for an optimal coolant flow rate of 1 l/m, optimal coolant inlet temperature lies between 40 and 50 °C.
Keywords :
CFD , Pareto optimality , Manifold microchannel heat sink , Exergy , Electronics cooling , Electronic reliability