    Two-phase refrigerant distribution in a parallel flow minichannel heat exchanger having horizontal headers

  • Author/Authors

    Nae-Hyun Kim، نويسنده , , Eul-Jong Lee، نويسنده , , Ho-Won Byun، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2012
  • Pages
    13
  • From page
    7747
  • To page
    7759
  • Abstract
    The refrigerant R-134a flow distributions are experimentally studied for a round header-ten flat tube test section simulating a brazed aluminum heat exchanger. Three different inlet orientations (parallel, normal, vertical) are investigated. Tests are conducted with downward flow for the mass flux from 70 to 130 kg/m2 s and quality from 0.2 to 0.6. Tubes are protruded to the center of the header. It is shown that the preferred inlet configuration is dependent on mass flux or quality. At low mass flux or quality, vertical inlet yields the best flow distribution, followed by normal and then parallel inlet. As mass flux or quality increases, the optimum configuration switches to normal inlet configuration. As compared with the flush-mounted configuration, more uniform flow distribution is obtained for the present protruded configuration. Possible explanation is provided based on flow visualization results. Correlations are developed to predict the fraction of liquid or gas taken off by downstream channel as a function of header gas Reynolds number at immediate upstream.
  • Keywords
    Flow distribution , Header , Heat exchanger , Inlet configuration
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
  • Serial Year
    2012
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER