Title of article :
Boron rejection in SWRO at high pH conditions versus cascade design Original Research Article
Author/Authors :
M. Faigon، نويسنده , , D. Hefer، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Pages :
7
From page :
10
To page :
16
Abstract :
Orthoboric acid dissociation, which affects boron rejection in RO membranes, depends on salinity, temperature and pH. Lately, increasing demand of permeate low boron concentration raises questions regarding the optimal method for boron removal in both technical and economical aspects. Several methods were presented in previous papers for boron removal, using RO membranes (SW & BW RO), at elevated pH and/or ion exchangers. In this paper, tests results of a full scale plant operation will be presented, at elevated pH of sea water feed to the RO membranes. Further, a techno-economical comparison will be presented, comparing two options for boron removal: SWRO operation at elevated pH versus Cascade design (IDE’s patented design).
Keywords :
Sea water RO , Boron removal , Cascade design , High pH operation
Journal title :
Desalination
Serial Year :
2008
Journal title :
Desalination
Record number :
1111460
Link To Document :
بازگشت