Title of article :
Experimental setup for precise measurement of losses in high-temperature superconducting transformer
Author/Authors :
Z. Janu، نويسنده , , J. Wild، نويسنده , , P. Repa، نويسنده , , Z. Jelinek، نويسنده , , F. Zizek، نويسنده , , L. Peksa، نويسنده , , F. Soukup، نويسنده , , R. Tichy، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2006
Pages :
3
From page :
759
To page :
761
Abstract :
A simple cryogenic system for testing of the superconducting power transformer was constructed. Thermal shielding is provided by additional liquid nitrogen bath instead of super-insulation. The system, together with use of a precise nitrogen liquid level meter, permitted calorimetric measurements of losses of the 8 kVA HTS transformer with a resolution of the order of 0.1 W.
Keywords :
Superconducting transformer , AC losses , Calorimeters