Title of article
The three-phase 75 m long HTS power cable Original Research Article
Author/Authors
S.T. Dai، نويسنده , , L.Z. Lin، نويسنده , , Y.B. Lin، نويسنده , , Z.Y. Gao، نويسنده , , Y.F. Fang، نويسنده , , L.H. Gong، نويسنده , , Y.P. Teng، نويسنده , , F.Y. Zhang، نويسنده , , X. Xu، نويسنده , , G. Li، نويسنده , , L.F. Li، نويسنده , , L.Y. Xiao، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2007
Pages
4
From page
402
To page
405
Abstract
A 75 m, three-phase HTS power cable is successfully demonstrated in a distribution grid of Gansu Changtong Cable Science and Technology Joint Stock Co., Ltd. in northwest China. The HTS power cable operates at a local live distribution grid of 6.6 kV to supply electric power for Changtong’s factory in Baiyin, Gansu Province. The cable was rated for voltages up to 10.5 kV, and has conducted up to 1600 A at 400 V, which was limited only by the load available at Changtong’s factory. The critical current of cable was tested as high as 5300 A DC at 76 K. The cable was connected to a local distribution grid to supply the power for the workshops at Changtong’s factory. The cable operates stably and reliably over 5500 h since December 2004.
Keywords
High Tc superconductor , Superconducting cable , Power application
Journal title
Cryogenics
Serial Year
2007
Journal title
Cryogenics
Record number
1172778
Link To Document