Title of article
Computational analysis of reduced-mixing personal ventilation jets
Author/Authors
Jackie S. Russo، نويسنده , , Thong Q. Dang، نويسنده , , H. Ezzat Khalifa، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2009
Pages
9
From page
1559
To page
1567
Abstract
In this paper we develop a detailed computational fluid dynamics (CFD) model of a personal ventilation (PV) setup comprising a PV nozzle, seated thermal manikin and floor diffuser, then use experimental velocity and tracer gas concentration data for the same setup to validate the CFD model. Specifically, we compare CFD results with the experimental results obtained with both a conventional round nozzle and a novel low-mixing co-flow nozzle directing a PV fresh air jet toward the breathing zone (BZ) of a seated thermal manikin in a thermally controlled chamber ventilated also by a floor diffuser behind the manikin. The CFD model shows excellent agreement with the experimental data. We then exercise the CFD model to study the effect of nozzle exit boundary conditions such as turbulence intensity and length scale, flow rate and temperature, and manikin temperature on the air quality in the BZ of the heated manikin. It is shown that the air quality of the novel PV system is sensitive to the nozzle exit turbulence intensity and flow rate, and insensitive to jet temperature within the 20–26 °C range, and to body temperature within a clo range of 0–1. A companion paper presents in detail the experimental set up and results used to validate the CFD model discussed in this paper.
Keywords
Air quality , ventilation , Personalized ventilation
Journal title
Building and Environment
Serial Year
2009
Journal title
Building and Environment
Record number
1217663
Link To Document