• Title of article

    Contribution of natural ventilation in a double skin envelope to heating load reduction in winter

  • Author/Authors

    Yu-Min Kim، نويسنده , , Soo-Young Kim، نويسنده , , Sung-Woo Shin، نويسنده , , Jang-Yeul Sohn، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    9
  • From page
    2236
  • To page
    2244
  • Abstract
    This study examined the contribution of a double skin envelope (DSE) to the heating energy savings brought about by natural ventilation in office buildings. A DSE was applied to the east- and west-facing walls on an actual three-floor building. Field measurements and computer simulations were performed in winter. The results implied that the DSE on the west-facing wall contributed to energy savings when natural ventilation was supplied from the cavity to the indoor space. The DSE facing east was not recommended for energy savings by natural ventilation because of its smaller exposure to solar irradiance. Multiple linear regression models were developed based on field measurements to predict the temperature variation in the cavities, and effective control logics will be discussed in a future study. Of all variables, the outdoor air temperature was the most significant factor influencing the air temperature in the cavity. Computer simulation indicated that the air in the cavity was heated to the required temperature without consuming additional energy when the ratio of the diffused irradiance to global irradiance was smaller than 0.69. The cavity in the DSE worked as a thermal buffer zone and contributed to reducing heating energy consumption by 14.71% in January.
  • Keywords
    Double skin envelope , Heating load , Natural ventilation , ENERGY SAVING
  • Journal title
    Building and Environment
  • Serial Year
    2009
  • Journal title
    Building and Environment
  • Record number

    1217739