Title of article :
Influence of fire source locations on the actuation of wet-type sprinklers in an office fire
Author/Authors :
Chi-Ming Lai، نويسنده , , Hung-Chi Su، نويسنده , , Ming-Ju Tsai، نويسنده , , Chien-Jung Chen، نويسنده , , Chun-Ta Tzeng، نويسنده , , Ta-Hui Lin، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Abstract :
An experiment is conducted on a full-scale model office and an actual sprinkler system to explore the influence of fire source locations on sprinkler actuation. The office space is a brick structure that measures 5.7 m in interior length, 4.7 m in width and 2.4 m in ceiling height, and equipped with a sprinkler system. The investigated fire source (100 kW LPG burner) locations include the room center, wall centers, room corner, and other locations at different distances from sprinklers. The results show that actuation of the sprinklers is affected by the fire source locations and the heat conduction properties of the glass temperature-sensing bulb. Average actuation time of all the tests is 102 s, around 40 s faster than if the fire source is located in the room center. For fire sources in corners, sprinklers are quickly activated at the experimental time 75 s, showing concentrated hot gas flow.
Keywords :
Office , Sprinkler , Fire source location , fire
Journal title :
Building and Environment
Journal title :
Building and Environment