Title of article
Performance analysis of a ground-assisted direct evaporative cooling air conditioner
Author/Authors
Ghassem Heidarinejad، نويسنده , , Vahid Khalajzadeh، نويسنده , , Shahram Delfani، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2010
Pages
9
From page
2421
To page
2429
Abstract
In this paper, the results of performance analysis of a ground-assisted hybrid evaporative cooling system in Tehran have been discussed. A Ground Coupled Circuit (GCC) provides the necessary pre-cooling effects, enabling a Direct Evaporative Cooler (DEC) that cools the air even below its wet-bulb temperature. The GCC includes four vertical ground heat exchangers (GHE) which were arrayed in series configuration. In order to have an accurate prediction of the optimum performance of a GCC, a computational fluid dynamic simulation was performed. Simulation results revealed that the combination of GCC and DEC system could provide comfort condition whereas DEC alone did not. Based on the simulation results the cooling effectiveness of a hybrid system is more than 100%. Thus, this novel hybrid system could decrease the air temperature below the ambient wet-bulb temperature. This environmentally clean and energy efficient system can be considered as an alternative to the mechanical vapor compression systems.
Keywords
Ground coupled circuit (GCC) , Cooling coil unit (CCU) , computational fluid dynamics (CFD) , Direct evaporative cooling (DEC) , Hybrid cooling air conditioner
Journal title
Building and Environment
Serial Year
2010
Journal title
Building and Environment
Record number
1218019