Title of article :
Air tightness measurement with transient methods using sudden expansion from a compressed chamber
Author/Authors :
Min-Jung Lee، نويسنده , , Nam Il Kim، نويسنده , , Hong Sun Ryou، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
9
From page :
1937
To page :
1945
Abstract :
Air tightness in an escape route of a building is important in preventing a fatal disaster by smoke spreading during a fire. To measure air tightness, transient methods using sudden air expansion from a small compressed air chamber into a room are proposed. Pressure variations in the chamber and the room are measured, and effective leakage areas are evaluated using differential and integral transient methods. The results of the two transient methods are compared with results from a typical steady method using an external blower fan. As a result, it was confirmed that all three experimental methods show good linearity between the imposed open hole area and the estimated effective leakage area. Therefore, the effective leakage area estimated using the transient methods could be converted to the equivalent leakage area of the steady method. The transient methods proposed in this study are expected to be more conveniently adopted for measuring air tightness if a suitable conversion factor is preliminarily evaluated.
Keywords :
fire safety , Air tightness measurement , Smoke suppression , Effective leakage area