• Title of article

    Operational characteristics of residential and light-commercial air-conditioning systems in a hot and humid climate zone

  • Author/Authors

    Brent Stephens، نويسنده , , Jeffrey A. Siegel، نويسنده , , Atila Novoselac، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2011
  • Pages
    12
  • From page
    1972
  • To page
    1983
  • Abstract
    Forced-air space-conditioning systems are ubiquitous in U.S. residential and light-commercial buildings, yet gaps exist in our knowledge of how they operate in real environments. This investigation strengthens the knowledge base of smaller air-conditioning systems by characterizing a variety of operational characteristics measured in 17 existing residential and light-commercial air-conditioning systems operating in the cooling mode in Austin, Texas. Some key findings include: measured airflow rates were outside of the range recommended by most manufacturers for almost every system; actual measured cooling capacities were less than two-thirds of rated cooling capacities on average; hourly fractional operation times increased approximately 6% for every °C increase in indoor–outdoor temperature difference; and lower mean indoor surrogate thermostat settings and higher supply duct leakage fractions were most associated with longer operation times. The operational characteristics and parameters detailed herein provide insight into the magnitude of the effects of HVAC systems on both energy consumption and indoor air quality (IAQ) in residential and light-commercial buildings.
  • Keywords
    Cooling energy use , Household energy , HVAC systems , Modeling input parameters , Field measurements
  • Journal title
    Building and Environment
  • Serial Year
    2011
  • Journal title
    Building and Environment
  • Record number

    1218252