• Title of article

    CFD study on the transmission of indoor pollutants under personalized ventilation

  • Author/Authors

    Chong Shen، نويسنده , , Naiping Gao، نويسنده , , Tingquan Wang، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2013
  • Pages
    10
  • From page
    69
  • To page
    78
  • Abstract
    As an advanced and efficient ventilation method, personalized ventilation (PV) has attracted more and more attentions. This paper investigates the pollutant transmission characteristics and personal exposure under the combination of two types of PV terminals and three kinds of typical background ventilation systems in an office with four work stations. Three kinds of cases are simulated and analyzed, including the most unfavorable condition, the most favorable condition and the ordinary condition. The results show that the interactions between PV and displacement ventilation (DV) or PV and under-floor air distribution (UFAD) are obviously stronger than that between PV and mixed ventilation (MV). Under a constant total ventilation rate, PV with a high flow rate may disrupt the characteristics of the background ventilation system and increase the personal exposure if comparing with the background ventilation alone. The advantage of PV depends on the proper combination of PV and its background ventilation system.
  • Keywords
    Pollutant transmission , Indoor air quality , CFD , Personal exposure , Personalized ventilation
  • Journal title
    Building and Environment
  • Serial Year
    2013
  • Journal title
    Building and Environment
  • Record number

    1218775