• Title of article

    Investigation of particle transport in offices equipped with ceiling-mounted personalized ventilators

  • Author/Authors

    A. Makhoul، نويسنده , , K. Ghali، نويسنده , , N. Ghaddar، نويسنده , , W. Chakroun، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2013
  • Pages
    11
  • From page
    97
  • To page
    107
  • Abstract
    The performance of ceiling-mounted personalized ventilators (PV) in reducing particle migration between office stations was assessed. The PV nozzles were integrated with peripheral diffusers that were able to form a canopy of conditioned air around the occupant. A numerical CFD model was developed to simulate the flow, temperature and particle concentration fields. Validation against experimental measurements and published experimental data was performed. The canopy was effective in reducing the migration of particles from the macroclimate to the microclimate region and low intake fractions of 1.90 × 10−4 and 5.9 × 10−4 were achieved for particle sizes of 1 μm and 0.01 μm, respectively. The PV jet was capable of maintaining an intake fraction of 3.6 × 10−4 for fine particle sizes (1 μm) and 2.95 × 10−4 for ultrafine particles (0.01 μm) when the particle-emitting source is in the proximity of the occupant. However, in spite of the good inhaled air quality achieved by the PV nozzle, the particle deposition rate on solid surfaces that are easily reached by the occupant is high when the source is placed in the microclimate.
  • Keywords
    Particle transport , Personalized ventilation , Localized air-conditioning , Indoor air quality
  • Journal title
    Building and Environment
  • Serial Year
    2013
  • Journal title
    Building and Environment
  • Record number