Title of article
Magnetic fields and induced voltages in case of a direct strike—comparison of results obtained from measurements at a scaled building to those of IEC 62305-4
Author/Authors
A. Kern، نويسنده , , F. Heidler، نويسنده , , M. Seevers، نويسنده , , W. Zischank، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2007
Pages
7
From page
379
To page
385
Abstract
In the paper the results obtained from experiments at a modelled reinforced building in case of a direct lightning strike are compared with calculations. The comparison includes peak values of the magnetic field , its derivative and of induced voltages in typical cable routings.
The experiments are performed at a 1:6 scaled building and the results are extrapolated using the similarity relations theory. The calculations are based on the approximate formulae given in IEC 62305-4 and have to be supplemented by a rough estimation of the additional shielding effect of a second reinforcement layer.
The comparison shows that the measured peak values of the magnetic field and its derivative are mostly lower than the calculated. The induced voltages are in good agreement. Hence, calculations of the induced voltages based on IEC 62305-4 are a good method for lightning protection studies of buildings, where the reinforcement is used as a grid-like electromagnetic shield.
Keywords
Calculations , Directlightningstrike , Electromagneticshield , Inducedvoltages , Magneticfields