Title of article :
On the interception of lightning flashes by power transmission lines
Author/Authors :
Liliana Arevalo، نويسنده , , Mahbubur Rahman and Vernon Cooray، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
8
From page :
220
To page :
227
Abstract :
The design of the lightning protection system LPS of transmission lines is based on the well known electro-geometrical model. The electro-geometrical model assumes that the first point on a power transmission line that will come within striking distance of the tip of a down-coming stepped leader channel is the strike point of the lightning flash. The model neglects almost all of the physics associated with the lightning attachment. Nowadays, as it is possible to use modern hardware and software tools and several different numerical methods, it is feasible to apply the physics of the discharge process to the study of lightning attachment. Such models take into account the movement of the downward and the resulting upward leaders from different points on the structures under consideration. In this paper, a procedure based on lightning physics was used to analyze the lightning attachment phenomena in EHV transmission lines of 230 kV and 500 kV and the results were compared with the predictions of the electro-geometrical method.
Keywords :
Lightningprotection , Lightningphysics , Transmissionlines , Shieldingconductor , Upwardleader , Interception
Journal title :
JOURNAL OF ELECTROSTATICS
Serial Year :
2011
Journal title :
JOURNAL OF ELECTROSTATICS
Record number :
1265274
Link To Document :
بازگشت