Title of article
Maximum mass flow ratio due to secondary flow choking in an ejector refrigeration system
Author/Authors
Chou، نويسنده , , S.K. and Yang، نويسنده , , P.R. and Yap، نويسنده , , C.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2001
Pages
14
From page
486
To page
499
Abstract
The occurrence of flow choking in an ejector of an ejector refrigeration system (ERS) was analysed and a model for predicting the maximum flow ratio of the ejector was developed. The multi-parameter equation to calculate the mass flow ratio takes into account the performance of the primary nozzle, the flow entrainment and mixing relating to ejector geometry and operating conditions. We validated the model using the reported experimental data of refrigerant R113, R141b and steam ERS. The present model was shown to provide better accuracy compared with results obtained by applying the existing 1-D ejector theory. We discussed the application of the model and highlighted the significance of the parameters for future work.
Keywords
Calcul , Performance , Refrigerating system , Ejector system , Modélisation , Modelling , CALCULATION , Système frigorifique , système à éjecteur , Performance
Journal title
International Journal of Refrigeration
Serial Year
2001
Journal title
International Journal of Refrigeration
Record number
1338907