• Title of article

    A comparison of hot-gas by-pass and suction modulation method for partial load control in refrigerated shipping containers

  • Author/Authors

    Tso، نويسنده , , C.P. and Wong، نويسنده , , Y.W and Jolly، نويسنده , , P.G and Ng، نويسنده , , S.M، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2001
  • Pages
    10
  • From page
    544
  • To page
    553
  • Abstract
    Simulation studies using a mathematical model are made to compare the performance of the hot-gas by-pass control and the suction modulation control in refrigerated shipping containers. Key factors such as compressor power draw, coefficient of performance and the sensible heat factor of evaporator coil against variations in container load, set-point and ambient temperatures are examined. Results show that the suction modulation control strategy is the more energy efficient of the two. The evaporator performance is found to be largely unaffected by either strategy. The analysis indicates the possibility of controlling relative humidity in the cargo space by variation of the superheat level.
  • Keywords
    Refrigerated transport , container , Capacity reduction , Design , Transport frigorifique , équipement frigorifique , réduction de puissance , Conception , Conteneur , Refrigerating equipment
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2001
  • Journal title
    International Journal of Refrigeration
  • Record number