    A method for evaluating the heat and mass transfer characteristics in a reversibly used water cooling tower (RUWCT) for heat recovery

  • Author/Authors

    Tan، نويسنده , , Kunxiong and Deng، نويسنده , , Shiming، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2002
  • Pages
    10
  • From page
    552
  • To page
    561
  • Abstract
    In sub-tropical regions, a standard water cooling tower may be reversibly used, as part of a desuperheater heat recovery system for service hot water heating, to extract free heat from ambient air in colder seasons when building cooling load is reduced. Chilled water is pumped into a reversibly used water cooling tower (RUWCT) where it is heated by warmer ambient moist air. This paper presents a method by which the heat and mass transfer characteristics in a counter-flow RUWCT can be evaluated. The method is developed by introducing to the Merkelʹs equation for standard water cooling towers the revisions that account for the differences in heat and mass transfer characteristics between a water cooling tower and a RUWCT. Field experimental results from a RUWCT installed in a sub-tropical region in China indicated that the method developed could be used to evaluate the thermal performance of a RUWCT with an acceptable accuracy.
  • Keywords
    heating , Reversible , Transfert de masse , Transfert de chaleur , Calcul , Refroidissement , Chauffage , Réversibilité , Cooling Tower , Mass transfer , Heat transfe , CALCULATION , COOLING , Tour de refroidissement dיeau atmosphérique
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2002
  • Journal title
    International Journal of Refrigeration
  • Record number