Title of article :
Experimental investigation on the drop-in performance of R407C as a substitute for R22 in a screw chiller with shell-and-tube heat exchangers
Author/Authors :
Lee، نويسنده , , D.-Y and Ahn، نويسنده , , Y and Kim، نويسنده , , Y and Kim، نويسنده , , Y and Chang، نويسنده , , Y.-S and Nam، نويسنده , , L، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Abstract :
A drop-in test of a mixed refrigerant R407C is performed in a commercial screw chiller with shell-and-tube heat exchangers originally designed for R22. The test results show a severe performance reduction when substituting the refrigerant from R22 to R407C. The reason for the performance reduction is analyzed comprehensively, and the influence of thermodynamic properties, compressor efficiency, and heat transfer is evaluated quantitatively. The major factor causing the performance reduction is assessed as the degradation of the heat transfer in using the mixed refrigerant, R407C. The heat transfer degradation in the evaporator is found to be larger and influences more on the chiller performance reduction. The performance reduction caused by the evaporator is approximately two times compared with that of the condenser.
Keywords :
Refrigerant , R22 , Substitute , R407C , Measurement , Refroidisseur dיeau , Compresseur à vis , Frigorigène , R22 , Performance , Substitut , R407C , Remplacement immédiat , Water chiller , Performance , Screw compressor , Mesure , Drop-in
Journal title :
International Journal of Refrigeration
Journal title :
International Journal of Refrigeration