Title of article :
Mass transfer correlation of NH3–H2O bubble absorption
Author/Authors :
Tae Kang، نويسنده , , Yong and Nagano، نويسنده , , T. and Kashiwagi، نويسنده , , Takao، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Pages :
9
From page :
878
To page :
886
Abstract :
The objectives of this paper are to study the effect of key parameters on absorption performance and to develop an experimental correlation of mass transfer coefficient for ammonia–water bubble absorption. The orifice diameter, liquid concentration and vapor velocity are considered as the key parameters. This study successfully visualized the bubble behavior and measured the volumetric diameter of bubbles during the bubble absorption process. The bubble absorption is grouped into two processes, bubble growth (process I) and bubble disappearance (process II), respectively. The following conclusions were drawn from the present study. A new experimental correlation for the volumetric bubble diameter was proposed with ±15% error band, which could be applied to calculate the mass transfer coefficient. The mass transfer coefficient increased with a decrease of the liquid concentration. In process II, the mass transfer coefficient increased with an increase of the Galileo number. Finally, experimental correlations of mass transfer coefficient were developed for processes I and II with ±18% error bands.
Keywords :
Ammoniac , Bulle , SOLUTION , Modélisation , heat transfer , Ammonia , Bubble , SOLUTION , water , Modelling , Transfert de masse , EAU
Journal title :
International Journal of Refrigeration
Serial Year :
2002
Journal title :
International Journal of Refrigeration
Record number :
1339477
Link To Document :