• Title of article

    Prediction of air coil performance under partially wet and totally wet cooling conditions using equivalent dry-bulb temperature method

  • Author/Authors

    Wang، نويسنده , , Jianfeng and Hihara، نويسنده , , Eiji، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    9
  • From page
    293
  • To page
    301
  • Abstract
    This paper mainly deals with the cooling and dehumidifying performance of air coils used in refrigeration and air-conditioning systems. A new method, equivalent dry-bulb temperature (EDT) method, is proposed for calculating the heat and mass transfer and for predicting the cooling modes (totally wet, partially wet, and totally dry) of moist air over the coil surface. A numeric model is further developed and validated with the experimental data of plain fin air coils. The deviation in both the cooling capacity and the vapor condensate estimated by the model is within the range of ±10%, and the prediction for the cooling modes of moist air over the coil surfaces is fairly exact.
  • Keywords
    Condensation , Performance , Procédé , Calcul , Water chiller , Performance , Measurement , Process , Refrigerant , Parameter , Transfert de chaleur , Transfer de masse , refroidisseur dיair , air humide
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2003
  • Journal title
    International Journal of Refrigeration
  • Record number