• Title of article

    Influence of liquid receiver on the performance of reversible heat pumps using refrigerant mixtures

  • Author/Authors

    Rajapaksha، نويسنده , , Leelananda and Suen، نويسنده , , K.O، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2004
  • Pages
    10
  • From page
    53
  • To page
    62
  • Abstract
    A liquid receiver is normally included in reversible vapour compression heat pumps (RHPs) to temporarily store the excess refrigerant charge occurring due to change of operation mode. The presence of a liquid receiver influences the total amount of refrigerant charged into a system, and particularly when using refrigerant mixtures, could affect the system circulation composition. Using a computer simulation, this paper compares the performance of RHPs designed with and without a liquid receiver, when using R407C. It was shown that the presence of a receiver caused an increase in the positive shift in the circulating composition, resulting in improved capacity while reducing the system COP in both heating and cooling modes when compared to a system without a receiver.
  • Keywords
    Modelling , receiver , liquid , R-407C , Transient regime , Modélisation , Pompe à chaleur , Réservoir , Performance , liquide , R-407C , Régime transitoire , Heat pump , Performance
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2004
  • Journal title
    International Journal of Refrigeration
  • Record number