• Title of article

    Convective boiling pressure drop of refrigerant R-134a in horizontal smooth and microfin tubes

  • Author/Authors

    Filho، نويسنده , , Enio P.Bandarra and Jabardo، نويسنده , , José M.Saiz and Barbieri، نويسنده , , Paulo E.L.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2004
  • Pages
    9
  • From page
    895
  • To page
    903
  • Abstract
    Present study deals with the pressure drop of refrigerant R-134a under convective boiling conditions in horizontal smooth and microfinned (‘grooved’) copper tubes. Experiments have been carried out in an experimental set up developed for change of phase studies with a test section made out of 7.0, 7.93, and 9.52 mm external diameter, 1.5 m long copper tubes, electrically heated by tape resistors wrapped on the external surface. Mass velocities and refrigerant qualities varied in the following ranges: 70–1100 kg s−1 m−2 and 5–95%. The annular flow pattern has been observed to occur over most of the operational conditions. For smooth tubes, the Jung and Radermacher correlation for the liquid two phase flow multiplier fits with reasonable precision the experimental data. As for grooved tubes, a correlation of the two phase flow multiplier in terms of the Martinelliʹs parameter has been developed which fits the data with an average absolute deviation of the order of 6.3%. The proposed correlation fits with good precision data obtained elsewhere for grooved tubes of different diameter and microfin geometry.
  • Keywords
    tube aileté , R-134a , Tube horizontal , Measurement , Pressure drop , R-134a , Boiling , Horizontal tube , Expérimentation , finned tube , Mesure , Chute de pression , Ebullition , Experiment
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2004
  • Journal title
    International Journal of Refrigeration
  • Record number